Addressable input module Rubezh AM-4-R3
R3 addressable module with 4 dry-contact inputs: four addresses in one housing, powered from the addressable loop.
Specifications
- Protocol
- R3 (RUBEZH R3)
- Inputs (loops)
- 4, each with its own address (4 consecutive addresses)
- Input type
- dry contact, NC or NO
- Loop types
- fire, intrusion, technical, fault
- Sensors per loop
- 1–2, with a shunt resistor
- Line to the sensor
- up to 100 m
- Power supply
- from the addressable loop, 0,6 mA
- Mounting
- DIN rail
- Housing
- IP30, 125×84×37 mm, −25…+55 °C
Description
The Rubezh AM-4-R3 addressable input module receives signals from devices with a dry-contact output that are not powered from the loop and transmits them to a Rubezh control panel via the R3 protocol. Functionally it is four AM-1-R3 addressable modules in one housing: the module occupies 4 consecutive addresses, and each loop has its own address. During configuration each loop is assigned a type — fire, intrusion, technical or “fault” — as well as an NC or NO contact type. One or two dry-contact sensors with a shunt resistor connect to a loop, and the line to the sensor can be up to 100 m long. The module is powered from the addressable loop and mounts on a DIN rail.
Advantages
- Four addressable inputs in one housing — fewer housings and less installation work, each loop reports its status with its own address
- Powered from the loop, 0,6 mA — power arrives over the addressable loop together with data
- Four loop types: fire, intrusion, technical, “fault” — one module for different sensors
- NC or NO contacts and adjustable “normal” and “activated” thresholds — tuning for a specific device
- Line to the sensor up to 100 m — the sensor can be placed away from the module
- DIN rail mounting — installation in an automation cabinet
Applications
- Monitoring the position of doors, gates and hatches in an R3 intrusion system
- Receiving alarm and fault signals from building equipment
- Connecting dry-contact outputs of other systems to a Rubezh addressable system
- Process monitoring in warehouses and production
- Automation cabinets collecting signals from several devices on a DIN rail
Frequently asked questions
How many addresses does AM-4-R3 occupy?
Can each input be given its own type?
Which module should be chosen for conventional detectors and a reader?
Related articles
- Wireless Addressable Fire Alarms: How the Rubezh R3 and Bolid S2000R Radio Links Work and When They Beat Cable
- SAT Solutions price index, September 2026: what makes up the budget for video surveillance, access control and fire alarms
- Uzbekistan's regulations on video surveillance, access control and fire alarms: a reference with document numbers
Product reviews
Questions & answers