Remote start device QR Systems UDP 513-02D (smoke extraction)
Addressable wireless RF 868 MHz remote start device for manual start of the smoke extraction system: CR123A and CR2032 batteries, range up to 900 m, XTEA 128-bit encryption.
Specifications
- Type
- remote start device, addressable wireless (smoke extraction)
- Interface
- RF 868 MHz, 5 channels, radiated power up to 25 mW
- Communication range
- up to 900 m in open terrain
- Encryption
- XTEA 128-bit
- Power supply
- main 3 V, CR123A 1500 mAh; backup 3 V, CR2032 210 mAh
- Battery life
- main at least 3 years, backup at least 3 months
- Pressing force
- at least 25 N
- Address slots
- 1
- Operating temperature
- −10 to +55 °C, humidity up to 93 % at +40 °C
- Housing
- IP20, 85×85×40 mm, max. 116 g
Description
The QR Systems UDP 513-02D remote start device is an addressable wireless device for manual start of the smoke extraction system in a QR Systems addressable fire alarm system. When the actuator is pressed with a force of at least 25 N, the device sends a signal over the RF 868 MHz radio channel to the control panel or, via the RR-02-250 radio expander, to the KS-02-250 system controller. Power is autonomous: a main CR123A battery and a backup CR2032 battery, both monitored by the system. The device occupies one address slot, is detected in the system automatically and is intended for QR Systems addressable systems with wireless devices.
Advantages
- RF 868 MHz radio channel, 5 channels, range up to 900 m in open terrain — communication with the panel without a wired line
- Protection against accidental activation: operates at a pressing force of at least 25 N — starts only on a deliberate press
- Two batteries: main CR123A (1500 mAh) for at least 3 years, backup CR2032 (210 mAh) for at least 3 months — both monitored
- XTEA 128-bit signal encryption — protected radio exchange with the panel
- Housing tamper monitoring (removal sensor) and LED status indication — device status visible on site
- Automatic detection in the system, service mode, 1 address slot — simple setup and maintenance
Applications
- Manual start of smoke extraction systems in a QR Systems addressable system
- Wireless fire alarm systems based on QR Systems PPK panels and the RR-02-250 radio expander
- Sites with the KS-02-250 system controller
- Buildings where the smoke extraction start button is connected without a wired line
- Extending existing QR Systems systems with wireless devices
Frequently asked questions
How does UDP 513-02D differ from UDP 513-02A and UDP 513-02P?
Which equipment does the device work with?
How long do the batteries last and what is included?
Related articles
Product reviews
Questions & answers