Addressable wireless manual call point QR Systems IP 513-02
Wireless manual call point RF 868 MHz: CR123A and CR2032 batteries, 3+ years of operation, range up to 900 m, 25 N actuation force, tamper, XTEA 128bit, IP20.
Specifications
- Type
- manual call point, addressable, wireless
- Interface
- RF 868 MHz, 5 channels
- Address slots
- 1
- Power supply
- main CR123A 3 V 1500 mAh; backup CR2032 3 V 210 mAh
- Operating time
- main at least 3 years, backup at least 3 months
- Radio range
- up to 900 m in open terrain, power no more than 25 mW
- Actuation force
- at least 25 N
- Encryption / tamper
- XTEA 128bit / opening sensor yes
- Operating temperature
- −10…+55 °C
- Housing
- IP20, 85×85×40 mm, 116 g
Description
The QR Systems IP 513-02 addressable wireless manual call point is designed for manual activation of the Fire signal in a QR Systems addressable fire alarm and fire suppression system. The call point operates under control of a fire control panel and is used with the RR-02-250 radio expander; communication is over the RF 868 MHz radio protocol with XTEA 128bit encryption, and the device occupies one address slot in the system. The signal is given by pressing the button with a force of at least 25 N, with protection against accidental activation. Power comes from a main CR123A battery (1500 mAh) and a backup CR2032 (210 mAh) with an operating time of at least 3 years and 3 months respectively; the state of both cells, housing opening and operability are monitored. The call point is installed indoors and is chosen by designers and installation companies for wireless QR Systems systems.
Advantages
- RF 868 MHz radio, 5 channels, range up to 900 m in open terrain — the call point is placed at the exit without laying a line
- Main CR123A battery for at least 3 years, backup CR2032 for at least 3 months — both cells monitored
- Actuation force of at least 25 N and protection against accidental activation — signal only by a deliberate press
- XTEA 128bit encryption — protected communication with the panel
- Housing tamper sensor and operability monitoring — the panel sees the call point status
- One address slot, 85×85×40 mm, 116 g, IP20, −10…+55 °C, average service life 10 years
Applications
- Wireless QR Systems addressable fire alarm in enclosed rooms
- Escape routes and exits in buildings with finished interiors where cabling is undesirable
- Manual activation of the Fire signal in QR Systems fire suppression systems
- Rented offices and retail premises with frequent re-planning
- Extending a wired QR Systems system with wireless devices via RR-02-250